This paper presents a method to compute the parameters of a transformer model with saturation using the voltage and current waveforms of an inrush test and a no-load test. The transformer is modeled with their electric and magnetic equivalent circuits and a single-valued function that characterizes its non-linear magnetic behavior. A 3-kVA single-phase transformer and a 5-kVA three-phase three-legged transformer have been tested in the laboratory. The method to obtain the parameters of the non-linear flux–current relation that characterize the saturation has been described in the paper. The analytical function used to adjust the experimental measurements fits them very well.
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
S. Bogarra, A. Font, I. Candela, J. Pedra,