Article ID Journal Published Year Pages File Type
704296 Electric Power Systems Research 2008 10 Pages PDF
Abstract

In trying to determine the available transfer capability (ATC), this paper primarily sets out to develop a fuzzy logic approach to parallelizing contingency-constrained optimal power flow (CCOPF). This algorithm may be used by utilities to optimize economy interchange for severe contingencies analyzed without disclosing details of their operating costs to competitors. In fact, the ultimate objective of fuzzy multi-objective CCOPF (FMCCOPF) is to carry out the minimization of both the base case (pre-contingency) operating cost and the post-contingency correction times as conflicting but fuzzy goals. Besides, the Benders decomposition is applied to partition the fuzzy formulation with contingency constraints, which allows for post-contingency corrective rescheduling, motivated by the improvement of computational efficiency using parallel processing. The feasibility of the proposed method is comprehensively realized by a comparison with the conventional optimal power flow (OPF) and the CCOPF with respect to the same array of transactions, base case, and generator/line outages for the IEEE-30 bus system and the IEEE-118 bus system.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
, , , , ,