Abstract

This paper reports a ferroresonant experience involving inductive voltage transformers (VT's) in a 400 kV substation equipped with circuit breaker grading capacitors. Field measurements are presented and compared with ATP/EMTP simulation results, showing very good agreement. A parametric analysis has been performed to investigate the effect of the substation capacitance on the occurrence of ferroresonance. Fundamental frequency and sub-harmonic ferroresonant modes have been identified and compiled in a bifurcation diagram. The methodology presented can be used to create risk maps of avoidable switching operations or substation configurations.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology