Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
705154 | Electric Power Systems Research | 2012 | 7 Pages |
This paper presents a new method for minimizing the number of PMUs and their optimal placement in power systems. The proposed method provides suitable constraints for power systems with two adjacent injection measurements (IMs). In addition, suitable constraints for considering the connection of two buses to each other and to an injection bus are proposed. The proposed constraints result in a reduction in the number of PMUs even though the system topological observability is complete. Existing conventional measurements are also considered. First, the number of PMUs is minimized in such a way that the system topological observability is complete. Then the optimal placement is done to maximize the measurements redundancy. The resulting phased to be installed in multiple stages. The optimal number of PMUs that ensure system topological observability under failure of a PMU or a line is also simulated. Simulations are performed on IEEE 30, 57 and 118 bus test systems by binary integer programming. The results show that the number of PMUs is equal to or less than the corresponding results of recently published papers, while the system topological observability is complete, and measurement redundancy is increased.
► Method for minimizing the number of PMUs and their optimal placement in power systems. ► Suitable constraints in power systems with two adjacent injection measurements (IMs). ► Suitable constraints for considering the connection of two buses to each other and to an injection bus.