Abstract
This paper presents a novel algorithm for identifying and measuring the symmetrical components of distorted three phase voltage or current waveforms in electrical power systems. The proposed algorithm is capable of estimating the symmetrical components as well as the harmonic contents of a given unbalanced distorted signal. The proposed technique is based on stochastic estimation theorem. The problem is formulated as an estimation problem and presented in state space form. The proposed algorithm used to estimate the positive, negative and zero components of unsymmetrical waveforms as well as the harmonic content of a given distorted signal. Application of the proposed algorithm has been conducted on various test cases. Among which a practical simulated power system has been implemented using EMTP. Various scenarios are carried out to simulate realistic situations of unsymmetrical waveforms. Effects of bad data on the solution accuracy are also studied. The speed of convergence is examined by changing the estimator initial conditions. Results obtained show that the proposed technique can estimate and track the symmetrical components of non-stationary three phase unbalance voltage or current waveforms in noisy environments. Fast accurate solutions are guaranteed regardless of the initial conditions. It is also shown that bad measurements have no effects on the final accuracy of the estimation.