| Article ID | Journal | Published Year | Pages | File Type |
|---|---|---|---|---|
| 7053591 | International Journal of Heat and Fluid Flow | 2016 | 10 Pages |
Abstract
The thermal performance of single-row heat exchangers is generally considered to be inferior to multi-row heat exchangers. It is therefore desirable to optimize the former; especially for those cases which cannot accommodate an alternative. In this study, the heat transfer performance of a single-row circular-finned tube heat exchanger was investigated experimentally under elevated disturbance levels. Specifically, grid-generated turbulence (GGT)-the characteristics of which had been measured beforehand with a hot-wire anemometer-was applied to a clean-flow benchmark case and measurements taken at the heat exchanger outlet. It was shown that when the grid is positioned appropriately, a mean enhancement (in global Nusselt number) of up to 11% can be achieved. Flow visualizations revealed the flow structures responsible for the increase in heat transfer.
Keywords
Related Topics
Physical Sciences and Engineering
Chemical Engineering
Fluid Flow and Transfer Processes
Authors
J.A. Moore, J.P.J. Stevenson, R. Grimes,