Article ID Journal Published Year Pages File Type
705411 Electric Power Systems Research 2013 6 Pages PDF
Abstract

A numerical calculation method based on the leader propagation model of lightning is proceeded to investigate the effect of overhead line tower geometric constructions to the lightning shielding failure. In this paper, the height and the spacing of the ground wire were changed to study the sensitivity of the shielding effectiveness on tower constructions. As the conclusion, an efficient layout scheme of ground wire and phase wire was proposed. Even if the protecting angle of the ground wire keeps unchanged, if the height of the ground wire is various, the total shielding failure rate is totally different, so we should take into account other factors except for the protection angle during the design of tower structure. This paper compared the total trip out rate of four types of double-circuit towers and concluded that the concave drum-type tower is the best design.

► This paper proposed a new numerical calculation method based on the leader propagation model of lightning to investigate the effect of overhead line tower geometric constructions to the lightning shielding failure. ► The sensitivity of the shielding effectiveness on tower constructions was studied and an efficient layout scheme of ground wire and phase wire was proposed. ► This paper compared the total trip out rate of four types of double-circuit towers and concluded that the concave drum-type tower is the best design.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
, , , , ,