Article ID Journal Published Year Pages File Type
705432 Electric Power Systems Research 2010 7 Pages PDF
Abstract

Thyristor Controlled Series Capacitor (TCSC) as a dynamic system, besides its capability in increasing power transfer in transmission lines, can be used to enhance different power system issues. In this paper, the effect of TCSC on voltage sag following transformer inrush current is investigated. It is shown that excessive transient inrush current occurring during transformer energizing can be mitigated by TCSC. Hence, voltage sag as one of the key components of the power quality is alleviated for the sensitive loads that are connected to the same bus which the power transformer is energized from. During a fault, TCSC can improve the voltage sag by limiting the current and help to keep the voltage as high as possible. Moreover, the inrush currents and the associated voltage sags that usually occur after clearing heavy single- or multistage faults are mitigated by the presence of TCSC. The model used for simulating inrush current is based on the characteristics of the major hysteresis loop out of which the internal trajectories are defined using the translation principal and a linear compensation to generate closed loops. An arctangent relation between the flux and the exciting current is defined. The expression parameters are deduced by curve fitting empirical data defining the major loop or the single-valued saturation characteristic.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
,