Abstract
This paper presents experimental results of lightning surges incoming into a customer due to lightning to an antenna of the customer, a pole and a ground nearby the customer, and briefly discusses lightning current distribution in the customer, a distribution line and a telephone line. Based on experimental results, modeling of each component is explained, and EMTP simulations are carried out. The ground voltage rise is represented by a mutual resistance between grounding electrodes. EMTP simulation results have been observed to agree qualitatively with the measured results, and it becomes possible to investigate lightning surges and current distribution in a customer by an EMTP simulation.
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
Akihiro Ametani, Kae Matsuoka, Hiroshi Omura, Yoshiyuki Nagai,