Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
705774 | Electric Power Systems Research | 2007 | 8 Pages |
Abstract
This paper proposes a phasor measurement algorithm for transmission systems compensated with shunt capacitor banks. Since the shunt capacitor banks tend to lower the resonant frequencies, the dominant component, which has the lowest resonant frequency, is insufficiently attenuated by a low-pass filter and has an adverse influence on the phasor measurement of the fundamental component in a fault current signal. This paper theoretically investigates the dominant frequency in the presence of shunt capacitor banks and presents a phasor measurement algorithm immune to the dominant component and DC-offset. The performance of the algorithm is evaluated for a-phase to ground (a-g) faults on a 154-kV transmission system compensated with shunt capacitor banks. The evaluation results indicate that the algorithm can measure the phasor reliably and satisfactorily, although the fault current signal is distorted with the dominant component and DC-offset. The paper concludes by describing the hardware implementation of the algorithm on a prototype unit based on a digital signal processor.
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
Soon-Ryul Nam, Sang-Hee Kang, Jong-Keun Park,