Article ID Journal Published Year Pages File Type
705880 Electric Power Systems Research 2008 9 Pages PDF
Abstract

This paper describes a phase-domain frequency domain technique to the harmonic analysis of a three-phase AC/DC system. The methodology is based on the harmonic multi-port network concept, expressed in terms of an ABCD parameter matrix which links voltage and current harmonics of different orders on both sides of the converter. Since the commutation angles are unknown, the harmonic interactions are computed by a sequential solution of the AC/DC system state variables, related by the ABCD matrix, and the updating of the commutation periods. A set of analytical equations has been derived to compute commutation times taking place in the converter. Test results are presented which demonstrate the effectiveness of the proposed methodology to assess harmonic interactions on both balanced and unbalanced operating conditions. The results are validated to those obtained by a time domain simulation.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
, , , ,