This work presents a series tapping station for integrating Offshore Wind Power Plants (OWPP) into a (Line Commutated Converter High Voltage Direct Current) LCC-HVDC transmission system. The tapping station allows to integrate wind power resources without building a new HVDC link and it is based on a Current Source Converter (CSC). However, the CSC requires a minimum DC current to extract the power coming from the OWPP which may not be guaranteed depending on the power conditions of the HVDC corridor. For this reason, this paper proposes a coordinated operation and control of the CSC and the OWPP. A steady-state analysis is performed to determine the appropriate AC voltage level of the CSC. A power reduction algorithm is presented to limit power extraction during a reduction in the current of the HVDC transmission system and under loss of communications between the CSC and the OWPP. The proposed algorithm and the performance of the system are validated through simulation results.