Article ID Journal Published Year Pages File Type
7115560 IFAC-PapersOnLine 2017 6 Pages PDF
Abstract
This paper describes the design strategy and testing results of a control system to improve damping of inter-area oscillations in the western North American Power System (wNAPS) in order to maintain dynamic stability of the grid. Extensive simulation studies and actual test results on the wNAPS demonstrate significant improvements in damping of inter-area oscillations of most concern without reducing damping of peripheral oscillations. The design strategy of the control system features three novel attributes: (1) The feedback law for the control system is constructed using real-time measurements acquired from Phasor Measurement Units (PMUs) located throughout the power grid. (2) Control actuation is delivered by the modulation of real power flow through a High Voltage Direct Current (HVDC) transmission line. (3) A supervisory system, integrated into the control system is in charge of determining damping effectiveness, maintaining failsafe operation, and ensuring that no harm is done to the grid.
Related Topics
Physical Sciences and Engineering Engineering Computational Mechanics
Authors
, , , ,