Article ID Journal Published Year Pages File Type
7121438 Measurement 2018 16 Pages PDF
Abstract
Condensing boilers are efficient for the utilization of natural gas. However, condensed droplets in flue gas are supercooled after condensation heat transfer, and direct contact devices cannot accurately measure the temperature of flue gas containing such droplets. Therefore, an in situ heating interlayer pumping device was designed. Experimental results showed that in situ heating interlayer pumping device can effectively filtered out the influence of supercooled droplets, the temperature of flue gas measured by the proposed device was about 3 °C higher than that measured by direct contact temperature measuring device; the device optimum flow rate was 0.35 L/min, optimum heat tracing temperature was in the range 100-140 °C; the effective reliability of the device was verified experimentally using the positive balance efficiency and the counter balance efficiency of 30-kW gas-fired condensing heat-transfer test platform.
Related Topics
Physical Sciences and Engineering Engineering Control and Systems Engineering