Abstract
The existing ejector cooling systems with thermal pumping effect (ECSTPEs) have severe problems of thermal energy and chilling load waste. The deviations of the initial ratio from its optimal value would lead to the deviations of the time length of cooling stage (TLCS), and finally, result in the performance deteriorations of the ECSTPEs. The results of the case study showed that, for an ECSTPE with R134a, a 10-second deviation from the optimal TLCS led to a decrease of 5.6% in the COP value and an increase of 23.7% in the chilling load, when the generation temperature, the condensing temperature and the evaporation temperature were 85 °C, 35 °C and 10 °C, respectively. Therefore, accurately controlling the TLCS corresponding to the optimal TLCS, which is derived on the basis of the optimal initial ratio, can effectively improve the performance of ECSPTEs.116
Related Topics
Physical Sciences and Engineering
Energy
Energy (General)
Authors
Yijian He, Yongjun Sun, Sheng Zhang, Yuanli Lyu, Guangming Chen,