The objective of this work is to study the primary control system of a hydropower plant operating isolated. The plant is modeled by differential equations and the results are compared with field data from an actual hydropower plant, with deviations lower than 1.0%. The study of the primary control system is conducted in order to define optimal parameters for the controllers. Four controllers are studied: traditional, PI, PID and PI-PD. The controllers’ performances are evaluated by stability criteria and a performance index. For the hydropower plant studied, the PI controller has the best performance.
Related Topics
Physical Sciences and Engineering
Engineering
Computational Mechanics
Authors
Maria Regina Gomes Zoby, Jurandir Itizo Yanagihara,