Article ID Journal Published Year Pages File Type
762660 Energy Conversion and Management 2005 18 Pages PDF
Abstract

Natural convection from uniformly heated helicoidal pipes oriented vertically and horizontally is experimentally studied. Four helicoidal pipes of different parameters are presented. The effects of pitch to pipe diameter ratio, coil diameter to pipe diameter ratio and length to pipe diameter ratio on the average heat transfer coefficient are found. The experiments covered a range of Rayleigh number based on tube diameter from 1.5 × 103 to 1.1 × 105. The results showed that the overall average Nusselt number, Num, increases with the increase in pitch to pipe diameter ratio, coil diameter to pipe diameter ratio and length to pipe diameter ratio for vertical helicoidal pipes. For horizontal helicoidal pipes, the overall average Nusselt number, Num, increases with the increase in pitch to pipe diameter ratio and length to pipe diameter ratio, but it decreases with the increase in coil diameter to pipe diameter ratio. New correlations are presented, and they can be used in HVAC applications.

Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
,