This paper presents the results of a study performed to develop a thermal modeling of radiant panels systems to be used in situ, as diagnosis tool in commissioning processes to determine the main operating conditions of the system in cooling or heating mode. The model considers the radiant panels as a finned heat exchanger in dry regime. By using as inputs the ceiling and room dimensions, the radiant ceiling material properties and the measurements of air and water mass flow rates and temperatures, the model is able to calculate the radiant ceiling capacity, ceiling surface average temperature, water exhaust temperature and resultant temperature as a comfort indicator. The modeling proposed considers combined convection, perforation effect and a detailed radiative heat exchange method for radiant ceiling systems. An example of each system considered in this study is shown, illustrating the validation of the model. A sensitive analysis of the model is performed.