Abstract

Unbalanced feeder systems may deteriorate of power quality, and increase investment and operating costs for distribution systems. The phase swapping method recommends re-phasing circuits of laterals and transformers for making the current and voltage balanced and also reducing feeder loss and voltage drop. In this paper, an application program, based on the automated mapping/facilities management/ geographic information system (AM/FM/GIS) is developed which contains a function of automatically computing Z-bus, load flow and phase balancing of feeders with phase swapping by using easily selecting of feeder on a graphic user interface application. Therefore, the relative data need not be keyed in manually. The presented phase balancing algorithm are based on database and related data structures developed on the AM/FM/GIS and Visual Basic software, which can be integrated into the Tai-Power distribution automation system. Then, the phase balancing algorithm is designed to handle the load patterns and the load of transformers that connect specific feeders when evaluating phase swaps that will result in reduced daily circuit losses over all load points. The proposed application not only can effectively reduce the circuit loss and improves phase balancing, but also enhances power quality efficiently under easily using environment.