Article ID Journal Published Year Pages File Type
772814 Energy Conversion and Management 2008 11 Pages PDF
Abstract

Experiments were performed to examine the spreading thermal resistance of centrally positioned heat sources and the thermal performance of a water charged, gravity assisted flat vapor chamber to be used for electronic cooling. Parametric studies including different heat fluxes and operating temperatures were conducted, and the effect of the relevant parameters on the cooling performance in terms of the spreading resistance was presented and discussed. The present vapor chamber heat spreader showed a heat removal capacity of 220 W/cm2 with a thermal spreading resistance of 0.2 °C/W.

Related Topics
Physical Sciences and Engineering Energy Energy (General)