Abstract

The liquid desiccant air conditioning system is drawing more and more attention due to its advantages in energy saving and environmental friendliness. The dehumidifier is one of the essential parts of the system, which affects the whole system performance severely. This paper experimentally studies the performance of the cross flow dehumidifier, which has been less studied than the counter flow dehumidifier, although it is more applicable in practice. Celdek structured packings were used in the dehumidifier, and a LiBr aqueous solution was used as the liquid desiccant. The moisture removal rate and dehumidifier effectiveness were adopted as the dehumidifier performance indices. The effects of the dehumidifier inlet parameters, including air and desiccant flow rates, air inlet temperature and humidity ratio and desiccant inlet temperature and concentration, on the two indices were investigated. Correlations are proposed to predict the cross flow dehumidifier performance, which give results in good agreement with the present experimental findings.