Article ID Journal Published Year Pages File Type
786883 International Journal of Refrigeration 2014 11 Pages PDF
Abstract

•The prototype steam ejector refrigerator can be stably operated in Thailand.•The prototype refrigerator was successfully tested as air conditioner.•CFD technique was employed to simulate the steam ejector used.

This paper presents the design and construction of a prototype steam ejector refrigeration system which can be operated under the actual condition of Thai environment, which is rather hot and humid. The prototype refrigerator was designed to produce a cooling capacity of approximately 3 kW. Water was selected to be used as the working fluid. The steam boiler used was a vertical fire tube type and it was designed to be used with LPG compact gas burner. The condenser was cooled by water obtained from a conventional cooling tower. The prototype refrigerator was used to produce chilled water which was used to cool a small tested room. It was observed that the room temperature of 24.2 °C was obtained at the cooling load of 3000 W. The cooling water was supplied to the condenser at about 30 °C. The COP obtained was 0.45. This prototype refrigerator is proven to be practical and can be used in actual environment of Thailand.

Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, ,