Article ID Journal Published Year Pages File Type
786901 International Journal of Refrigeration 2014 10 Pages PDF
Abstract

•The effects of vapor injection techniques of a CO2 heat pump are investigated.•The heating performance of the SCVI cycle is the highest and the most stable.•The optimum injection ratios are determined at various compressor frequencies.

The objective of this study is to investigate the effects of vapor injection techniques on the heating performance of a CO2 heat pump. The performances of the flash tank vapor injection (FTVI), sub-cooler vapor injection (SCVI) and FTVI with a suction line heat exchanger (FTSX) cycles were measured and analyzed with variations of the outdoor temperature, compressor frequency, and injection mass flow rate. At the outdoor temperature of −15 °C and compressor frequency of 55 Hz, the heating capacity and COP of the optimized SCVI cycle were 12.1% and 12.7% higher than those of the optimized FTVI cycle, respectively, because the total mass flow rate in the SCVI cycle was higher than that in the FTVI cycle by the large temperature and pressure differences in the sub-cooler of the SCVI cycle. In addition, the optimum injection flow rate ratios in the vapor injection CO2 cycles yielding the maximum COP were determined at various compressor frequencies.

Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , , , ,