Abstract

This study thermodynamically analyzed a cascade refrigeration system that uses carbon dioxide and ammonia as refrigerants, to determine the optimal condensing temperature of the cascade-condenser given various design parameters, to maximize the COP and minimize the exergy destruction of the system. The design parameters include: the evaporating temperature, the condensing temperature and the temperature difference in the cascade-condenser. The results agreed closely with the reported experimental data. The optimal condensing temperature of the cascade-condenser increases with TC, TE and ΔT. The maximum COP increases with TE, but decreases as TC or ΔT increases. Two useful correlations that yield the optimal condensing temperature of the cascade-condenser and the corresponding maximum COP are presented.