Article ID Journal Published Year Pages File Type
788729 International Journal of Refrigeration 2013 20 Pages PDF
Abstract

•Exergetic analyses of the developed desiccant-evaporative air-conditioning system.•Exergetic analyses based on different regeneration temperatures.•Exergetic performances for the system and components are shown.

The developed desiccant-evaporative air-conditioning system was evaluated using the exergetic method under controlled environmental conditions to determine the performances of the whole system and its components.Percentage contributions of exergy destruction of system components at different regeneration temperatures and reference temperatures were determined. Exergy destruction coefficient of different components at different regeneration and reference temperatures were presented. It was shown that exergetic performances varied with respect to the regeneration and reference temperatures. The exergetic performances based on thermal, electric, total exergy input, first definition and second definition efficiencies were shown.Based on the results, reference and regeneration temperatures affected the determination of the system performances and its components. It was shown that air-heating coil, air fans and desiccant wheel contributed to large percentage of exergy destruction. Hence, the mentioned components should be given attention for further improvement of the system performances.

Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , , , , ,