Abstract
The performance of a twin screw compressor operating under wet (two-phase) compression conditions in an ammonia–water compression absorption heat pump cycle is investigated both theoretically and experimentally. The paper reports on the influence of the location of liquid intake or, depending what applies, injection angle and mass flow rate of the injected liquid on compressor performance. Labyrinth seals separate the oil-free process side from oil lubricated bearing housing. Labyrinth seals leakage is modelled and its impact on performance is theoretically and experimentally investigated. The need for liquid injection from the discharge side to obtain acceptable performance is discussed based on experimental results.