Article ID Journal Published Year Pages File Type
789945 International Journal of Refrigeration 2008 10 Pages PDF
Abstract

This paper presents a general methodology for developing a steady-state detector for a vapor compression system based on a moving window and using standard deviations of seven measurements selected as features. The feature thresholds and optimized moving window size were based upon steady-state no-fault tests and startup transient tests. The study showed that evaporator superheat and condenser subcooling were sufficient for determining the onset of steady-state during the startup transient. However, they misidentified steady-state during indoor temperature change tests where evaporator saturation temperature and air temperature change across the evaporator were needed for proper steady-state identification. Hence, the paper recommends including all fault detection and diagnosis (FDD) features in the steady-state detector to ensure the robustness of the detector because different features may play key roles with different transients.

Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , , ,