Article ID Journal Published Year Pages File Type
7916621 Energy Procedia 2017 7 Pages PDF
Abstract
This study investigates the optimization and electricity savings of an air-cooled chiller system with mist coolers. An air-cooled screw chiller having a nominal capacity of 282 kW was retrofitted with a mist cooler and dual condenser fan controls: fixed head pressure with constant speed and floating condensing temperature with variable speed. Comprehensive operating data logged at 5-min intervals were used to develop chiller models by random forest. The models served as a fitness function for genetic algorithm to predict the maximum coefficient of performance (COP) with optimal controlled variables under various operating conditions. Scatter plots of the optimal variables against the actual variables showed that to achieve the maximum COP, the set point of condensing temperature should be adjusted based on its measured value and the variation of heat rejection airflow rate. The probability of applying mist cooling was identified to be 70.91 - 78.33% for the simulated cooling load distribution of a hotel in a subtropical climate. Mist coolers with the optimal control brought electricity savings of 2.28 - 8.16%, depending on system configurations and condenser fan control modes. Fewer chillers in a system would result in more electricity savings from the optimal control while mist coolers complement the frequent full load operation of chillers to enhance electricity savings.
Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, , , ,