Article ID Journal Published Year Pages File Type
792783 International Journal of Refrigeration 2010 9 Pages PDF
Abstract

This study investigated the flow boiling heat transfer of carbon dioxide inside a small-sized microfin tube (mean inner diameter: 2.0 mm; helix angle: 6.3°) at a saturation temperature of 15 °C, and heat and mass flux ranges of 4.5–18 kW m−2 and 360–720 kg m−2 s−1, respectively. Although, experimental results indicated that heat flux has a significant effect on the heat transfer coefficient, the coefficient does not always increase with mass flux, as in the case of conventional refrigerants such as HFCs or HCFCs. Under certain conditions, the heat transfer coefficient at a high mass flux was lower than that at a lower mass flux, indicating that convective heat transfer had a suppression effect on nucleate boiling. The heat transfer coefficients in the microfin tubes were 1.9∼2.3 times the values in smooth tubes of the same diameter under the same experimental conditions, and the dryout quality was much higher, ranging from 0.9 to 0.95. The experimental results indicated that using microfin tubes may considerably increase the overall heat transfer performance.

Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , ,