Article ID Journal Published Year Pages File Type
8071954 Energy 2018 31 Pages PDF
Abstract
This article presents a new control algorithm for an Intermittent Renewable Energy Systems coupled with an Energy Storage System (ESS) connected to a load and to the grid. It aims to limit grid power ramp-rate, to optimize energy trading and to manage the ESS State of Charge (SoC) under several constraints. The strategy uses a ramp-rate limiter algorithm with a SoC feedback control. The controller reference is optimized with a Dynamic Programming algorithm using weather and consumption predictions. Every 2 h, the optimization is refreshed with the actual SoC and new predictions. The algorithm is applied on real data measured in Ajaccio and shows a light improvement in the plant operation cost and ensures that the ESS is not depleted at the end of the day.
Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, , , ,