Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
8072147 | Energy | 2018 | 43 Pages |
Abstract
A conjugate heat transfer analysis of a double air channel solar chimney (SC-DC) aiming to determine the configuration that maximizes the mass flow rate of the system is presented. The design modifications consisted on two geometrical parameters: 1) the separation between the absorber wall and the glass covers that form the air channels (b), and 2) the height of the system (L). A code based on the Finite Volume Method was developed and a k-Ï turbulence model was used to model air turbulence in the SC-DC. The code was validated and it showed a good agreement with experimental data reported in the literature. We found that the optimal configuration of the SC-DC under the considered conditions is Lâ¯=â¯2â¯m and bâ¯=â¯0.125â¯m. The optimum L of the SC-DC is similar to the value reported for a conventional chimney, whereas the optimum b is smaller than the one of a conventional chimney. The optimal configuration of the SC-DC had a thermal efficiency of 38.5% and a mass flow rate of 0.1072â¯kg/s when it receives a beam solar radiation of 700â¯W/m2 and a diffuse solar radiation of 100â¯W/m2.
Related Topics
Physical Sciences and Engineering
Energy
Energy (General)
Authors
I. Zavala-Guillén, J. Xamán, I. Hernández-Pérez, I. Hernández-Lopéz, M. Gijón-Rivera, Y. Chávez,