Article ID Journal Published Year Pages File Type
8074259 Energy 2016 10 Pages PDF
Abstract
Canada has many isolated communities that are not connected to the electrical grid. Most of these communities meet their electricity demand through stand-alone diesel generators. Diesel generators have economic and environmental concerns that can be minimized by using hybrid renewable energy technologies. This study aims to assess the implementation of a hybrid energy system for an off-grid community in Canada and to propose the best hybrid energy combination to reliably satisfy electricity demand. Seven scenarios were developed: 1) 100% renewable resources, 2) 80% renewable resources, 3) 65% renewable resources, 4) 50% renewable resources, 5) 35% renewable resources, 6) 21% renewable resources, and 7) battery-diesel generators (0% renewable resources). A case study for the remote community of Sandy Lake, Ontario, was conducted. Hybrid systems were chosen to meet the requirements of a 4.4 MWh/day primary load with a 772 kW peak load. Sensitivity analyses were carried out to assess the impact of solar radiation, wind speed, diesel price, CO2 penalty cost, and project interest rate on optimum results. A GHG (greenhouse gas) abatement cost was assessed for each scenario. Considering GHG emission penalty cost, the costs of electricity for the seven scenarios are $1.48/kWh, $0.62/kWh, $0.54/kWh, $0.42/kWh, $0.39/kWh, $0.37/kWh, and $0.36/kWh.
Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, , , , ,