Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
8076561 | Energy | 2014 | 7 Pages |
Abstract
A variable effect absorption refrigeration cycle is proposed which can obtain a rising COP (Coefficient of Performance) versus the rising generation temperature. This novel cycle could be applied for solar absorption cooling efficiently. In this paper, a 50 kw variable effect (also named as 1.n effect) absorption chiller using LiBr-water as working fluid was designed. Its rated condition is generation temperature of 125 °C, condensation temperature of 40 °C, absorption temperature of 35 °C and evaporation temperature of 5 °C. The variable effect absorption chiller was then manufactured and tested. Data from the experiment showed that the chiller can get a rising COP from 0.69 to 1.08 under generation temperature from 95 °C to 120 °C as it was expected. The average error between theoretical COP and experimental COP was 7.3%. Feasibility of the variable effect absorption chiller and the effectiveness of the design have been verified.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Energy (General)
Authors
Z.Y. Xu, R.Z. Wang,