Article ID Journal Published Year Pages File Type
8088694 Geothermics 2018 10 Pages PDF
Abstract
The ground-source heat pump (GSHP) system using a horizontal ground heat exchanger (GHE) can be employed to reduce the installation cost and obtain a balance between efficiency and costs. Among the different types of horizontal GHEs, a spiral-coil-type GHE is one of the advantageous configurations in terms of thermal performance. However, there is no satisfactory guideline to design the horizontal spiral-coil GHEs, though design methods for other types of horizontal GHEs exist. Hence, in this study, a design method is proposed for the horizontal spiral-coil GHEs by modifying the boundary conditions of an existing equation. To verify the applicability of the proposed design equation, a laboratory thermal response test was conducted to validate the finite element model. Then, the validated numerical model was utilized for a computational fluid dynamics (CFD) simulation on an arbitrary building wherein a GSHP system with a horizontal spiral-coil GHE is operated. The entering water temperature (EWT) of 32.09 °C from the simulation result was lower than the design EWT criteria of 32.2 °C, implying that the thermal performance of the GHE for a month of operation is sufficient to cover the building load. The result provides the applicability of the proposed design method.
Related Topics
Physical Sciences and Engineering Earth and Planetary Sciences Geochemistry and Petrology
Authors
, , , ,