Abstract
Effects of fault type on SFCL FRT controller performance are analyzed and investigated in details. The proposed SFCL FRT controller has been tested under single phase, double phase, phase to phase, and three phases to ground faults. Results display that the three phases to ground fault is the most severe type on SFCL FRT performance from stability point of view. On the other hand, double phase to ground fault is the most severe one from fluctuations and oscillations points of view. Parameters of the SFCL must be adjusted based on the three phases to ground fault. If the SFCL FRT controller is designed to can deal with three phases fault, it sure can deal with the other fault types successfully.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Renewable Energy, Sustainability and the Environment
Authors
Rashad M. Kamel,