Abstract

The purpose of this study, through standard furnace fire tests and a natural fire test, is to analyze the heat insulation behavior of galvanized rolling shutters sprayed with intumescent coatings. The following experiments and associated estimations demonstrated that in the 1-h standard fire-resisting tests, the radiant heat flux at a measuring point horizontally 1 m away from the center of an unexposed surface the radiation could reach 4.64 W/cm2 for the traditional uninsulated galvanized rolling shutter, and that the radiant heat flux would be substantially decreased to 0.22 W/cm2 for one with intumescent coating of 0.3 mm target thickness, which, during the heating process, expanded about 100 times in volume and then generated a certain insulation effect. Therefore the intumescent coatings on galvanized rolling shutters have been proved by this study to be a feasible method of insulation, which can be applied in the future fire compartment design of buildings.

Related Topics
Physical Sciences and Engineering Engineering Engineering (General)