Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
9708190 | International Journal of Refrigeration | 2005 | 8 Pages |
Abstract
Detailed 2D CFD calculations for vapour flow field and rate of condensation are carried out for a geometry similar to a real shell-and-tube condenser with 100 tubes, with condensation on the shell-side. The differences in vapour flow behaviour are investigated for pure R22 and for a binary mixture of R32 and R134a, which has a gliding temperature difference of 5.5Â K. It is shown that, the flow field for a zeotropic mixture is significantly different from that for a pure fluid. The nature of the mixture flow causes the vapour and condensate to flow counter-currently in part of the condenser. Adjustments of the inlet design turn out to influence the rate of heat transfer by up to 24% for the conditions tested, with greater influence on heat transfer for lower driving forces.
Keywords
Related Topics
Physical Sciences and Engineering
Engineering
Mechanical Engineering
Authors
Tord Karlsson, Lennart Vamling,