Article ID Journal Published Year Pages File Type
9708216 International Journal of Refrigeration 2005 11 Pages PDF
Abstract
This paper also presents simulation results for the heat exchangers of an HCFC-22 window air conditioner with HC-290 as a drop-in substitute. The simulation has been carried out using EVAP-COND, a heat exchanger model developed by NIST [National Institute of Standards and Technology. EVAP-COND: simulation models for finned-tube heat exchangers, Maryland, USA (2003). http://www2.bfrl.nist.gov/software/evap-cond/[18]]. The simulated evaporator capacities are within ±4% of the experimentally measured cooling capacities for both refrigerants. Simulation results for HC-290 and HCFC-22 are compared. The exit temperatures of HC-290 are lower by 0.3-1.2 °C in the condenser and are higher by 2.1-2.4 °C in the evaporator than HCFC-22. Evaporating pressures of HC-290 are lower by 2.1-3.3% as compared to HCFC-22. The pressure drops of HC-290 are lower in both the evaporator and the condenser as compared to HCFC-22. The outlet temperatures of air for HCFC-22 and HC-290 in both heat exchangers are nearly the same.
Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , ,