Abstract
												For the purpose of protecting electric power system, many researches and developments of fault current limiters are being performed. The authors studied a dc hybrid three-phase fault current limiting interrupter (FCLI) composed of a superconducting reactor and an S/N transition element, connected in series each other. The dc hybrid type fault current limiting interrupter can limit a fault current by means of the inductance of high temperature superconducting (HTS) coil together with the normal transition of HTS bulk material (HTSB). In the case of an accident, the normal transition of the bulk material can be accelerated by the magnetic field of the HTS coil. In this paper, the dc hybrid type fault current limiting interrupter for 5.5 km long 6.6 kV-600 A power distribution system is analyzed, and performances of fault current limitation and interruption are confirmed. Moreover, a reclosing operation is discussed for this power distribution system.
											Related Topics
												
													Physical Sciences and Engineering
													Physics and Astronomy
													Condensed Matter Physics
												
											Authors
												Hongtian Shao, Tomoyuki Satoh, Mitsugi Yamaguchi, Satoshi Fukui, Jun Ogawa, Takao Satoh, Hiroyuki Ishikawa, 
											