Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
9951863 | Fusion Engineering and Design | 2018 | 9 Pages |
Abstract
Pressure drop is one basic issue for the heat-removal systems for high heat flux components, such as the ITER divertors in fusion reactors, in which an accurate knowledge of single-phase frictional pressure drop is fundamental for further calculation of two-phase frictional pressure drop. However, the single-phase frictional pressure drop is still not well examined under high heat fluxes. In this study, experiments were conducted on the single-phase frictional pressure drop of water flow in circular tubes within the range of qâ=â5-10âMW/m2, Gâ=â6000-10,000âkg/m2 s and pâ=â 3-5âMPa (typical operating parameters for water-cooled divertors). The data were correlated using the equation of f/fad =(μw/μb)m, in which m is an empirical exponent. It is found that the exponent m is affected by the length-to-diameter ratio of flow channel, while the effects of mass flux and heat flux are insignificant. In addition, a number of existing correlations for single-phase friction factor were compared with our data. The results indicate that these correlations cannot well capture part of the data. Therefore, a modified correlation is proposed to calculate the single-phase friction factor under high heat fluxes, in which the effect of length-to-diameter ratio is taken into account. The new correlation has an improved performance compared with the existing correlations.
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
Pengcheng Guo, Junhui Wang, Jianguo Yan, Xingqi Luo, Qincheng Bi,