Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
10127318 | Applied Thermal Engineering | 2018 | 46 Pages |
Abstract
Adjusting the heat and moisture of a conditioned space is important to maintain the comfort of the air. Adding or removing heat and moisture depends mainly on the heat and mass transfer characteristics within the system. In this study, the heat and mass transfer characteristics, in the form of the Nusselt number (Nu) and the Sherwood number (Sh), of a honeycomb desiccant dehumidifier (HDDH) were investigated experimentally. The HDDH was driven by using the honeycomb desiccant configuration, which was constructed from a polymer adsorbent material. The adsorption temperature (Tads) was considered as an adjustable parameter using values of 20â¯Â°C, 25â¯Â°C, and 35â¯Â°C. Each adsorption temperature was evaluated under the time intervals for the desorption and adsorption processes (switching time: Ï) of 60:60â¯min, 60:90â¯min, 60:120â¯min, and 90:120â¯min. For the given parameters, the desorption temperature and mass flow rate of the air were kept unchanged at 55â¯Â°C and 0.1â¯kg/s, respectively. The results showed that the Nu and Sh are more evenly responsive to change of adsorption temperature than switching time. Low desorption temperature results in high values of Nu and Sh. However, variation of switching time produces little change in Nu and Sh. Empirical correlations were also developed in this study. The empirical correlations matched the experimental data well.
Related Topics
Physical Sciences and Engineering
Chemical Engineering
Fluid Flow and Transfer Processes
Authors
Indri Yaningsih, Agung Tri Wijayanta, Takahiko Miyazaki, Shigeru Koyama,