Article ID Journal Published Year Pages File Type
10390531 Applied Thermal Engineering 2011 8 Pages PDF
Abstract
► Performance of major components in a water-loop heat pump system is analyzed in terms of power consumption vs. loop water temperature. ► It is proved that there exists a unique loop water temperature minimizing the total energy consumption. ► A minimum-searching strategy is adopted to find the optimal loop water temperature, and simulations show the strategy outperforms the conventional practice in cooling mode.
Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes