Article ID Journal Published Year Pages File Type
1046932 Energy for Sustainable Development 2012 9 Pages PDF
Abstract

The study presents an analysis aimed at choosing between off-grid solar photovoltaic, biomass gasifier based power generation and conventional grid extension for remote village electrification. The model provides a relation between renewable energy systems and the economical distance limit (EDL) from the existing grid point, based on life cycle cost (LCC) analysis, where the LCC of energy for renewable energy systems and grid extension will match. The LCC of energy feed to the village is arrived at by considering grid availability and operating hours of the renewable energy systems. The EDL for the biomass gasifier system of 25 kW capacities is 10.5 km with 6 h of daily operation and grid availability. However, the EDL for a similar 25 kW capacity photovoltaic system is 35 km for the same number of hours of operation and grid availability. The analysis shows that for villages having low load demand situated far away from the existing grid line, biomass gasification based systems are more cost competitive than photovoltaic systems or even compared to grid extension.

► Life cycle cost analysis of renewable energy systems and grid extension. ► Economical distance limit (EDL) for different renewable energy systems capacity. ► Sensitivity analysis of EDL on grid availability and operation hours.

Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, ,