Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
13429820 | International Journal of Electrical Power & Energy Systems | 2020 | 9 Pages |
Abstract
In recent years, zero-sequence overcurrent protection misoperated frequently when the high-impedance transformers are energized without load. This paper studies the characteristics of zero-mode inrush current of the high-impedance transformers, including amplitude and attenuation. Firstly, the corresponding relation of “winding arrangement - flux distribution - equivalent circuit parameters” of transformer was clarified. On the basis of analyzing single-phase and three-phase inrush current, the analytical expression and equivalent circuit of zero-mode inrush current were proposed. Then, according to the different winding arrangement, the different parameters of hollow inductance, self-leakage inductance and saturated mutual inductance of the high-impedance transformers and ordinary transformer were explained and calculated. Further, based on the different parameters and analytical expression, the zero-mode inrush current characteristics of high-impedance transformers were analyzed. The correctness of characteristic analysis of high-impedance zero-mode inrush current was verified via digital simulations and dynamic physical simulations tests.
Related Topics
Physical Sciences and Engineering
Computer Science
Artificial Intelligence
Authors
Wenbin Cao, Xianggen Yin, Zhe Zhang, Yuanlin Pan, Yuxue Wang, Xiangyuan Yin,