Article ID Journal Published Year Pages File Type
243825 Applied Energy 2011 7 Pages PDF
Abstract

This paper presents the results of an experimental analysis comparing the performance of a vapour compression refrigerating unit operating with R22, and its performance in comparison to a new HFC fluid, substituting the former according to Regulation No 2037/2000.In particular, the plant working efficiency was first tested with R22 and then with three new HFC fluids: R417A, R422A and R422D. The investigation verified that despite the case of substitution and the advantage of being able to continue to use mineral oil as a lubricant in the compressor, the performance with the new tested fluids did not result as efficient as when using R22.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
, ,