Article ID Journal Published Year Pages File Type
244091 Applied Energy 2011 14 Pages PDF
Abstract

As a part of a commissioning study, the chilled ceiling system of a large commercial building located in Belgium is evaluated. A representative office has been instrumented and data on the chilled ceiling system operating in real conditions have been collected. The simulation of the whole system is performed by means of a transient thermal model of the building and its HVAC system. The model considers the hydronic panels as a transient-state finned heat exchanger connected to a simplified lumped transient model of the building. The behavior of the hydronic ceiling system and the interactions with its environment (walls, ventilated facade, internal loads and ventilation system) has been experimentally and numerically evaluated. Commissioning test results show that the influence of surfaces temperatures inside the room, especially the facade, is considerable. Then, it is clear that the hydronic ceiling system must be evaluated together with its designed environment and not as a separate HVAC equipment.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
,