Article ID Journal Published Year Pages File Type
244227 Applied Energy 2011 11 Pages PDF
Abstract

This study presents a model-based control strategy for a novel dedicated outdoor air-chilled ceiling (DOAS-CC) system with the aim of optimizing the overall system performance. The DOAS-CC system incorporates liquid desiccant dehumidification and membrane-based total heat recovery technologies. Simplified but reliable models of major components in the DOAS-CC system are firstly developed to predict the system performance. A cost function is then constructed to minimize total energy consumption while properly maintaining thermal comfort reflected by indoor air temperature and relative humidity. Genetic algorithm is used to search for optimal set-points of the supply air temperature and humidity ratio of the dedicated outdoor air subsystem as well as the supply water temperature. The performance of this strategy is tested and evaluated with different control settings in a simulated multi-zone space served by the DOAS-CC system under various weather conditions. The results show that optimized control variables produced by the optimal strategy can improve the system energy performance and maintain indoor thermal comfort.

► Present an optimal control strategy for liquid desiccant based dedicated outdoor air-chilled ceiling system. ► Simplified models for optimal control are developed. ► Control variable set points are higher under optimal control than those of conventional control. ► Maintain comfort indoor environment and achieve significant energy saving.

Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
, , ,