Article ID Journal Published Year Pages File Type
400010 International Journal of Electrical Power & Energy Systems 2011 7 Pages PDF
Abstract

Grid connected EHV transformers experience various terminal disturbances when in service. The present work attempts to investigate the voltage stresses that may develop on the transformer insulations under a variety of terminal disturbances. A number of standard and non-standard wave shapes like lightning impulse, chopped lightning impulse, steep-front long tail switching surge and oscillatory transient over voltages have been simulated and impressed on the terminals of a 400 kV EHV power transformer operating in the Indian power grid to ascertain how the winding insulations are stressed under these disturbances. Relevant section of the Indian power grid and the transformer has been modeled using Alternative Transient Program (ATP). It has been established that oscillatory system transients can trigger natural resonate frequencies of the transformers causing high voltage stresses on the insulations. Short Time Fourier Transform (STFT) analysis of the oscillatory voltage response of the windings confirmed the presence of resonant frequencies indicating forced resonance. Some remedial measures involving winding design modifications have been suggested in the paper to overcome the problem.

► Switching events in power systems generate oscillatory transient over voltages. ► Transient over voltages may eventually excite internal resonances. ► Internal resonances produce high internal stresses within transformer windings. ► Pay attention to low amplitude oscillatory transients to protect transformers. ► Winding design modifications of transformer can reduce voltage stresses.

Related Topics
Physical Sciences and Engineering Computer Science Artificial Intelligence
Authors
, , ,