Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
4916706 | Applied Energy | 2017 | 12 Pages |
Abstract
In a central heating, ventilation, and air conditioning (HVAC) system, the set-points for several local control loops have a significant influence on the overall energy performance of the system. Real-time optimization (RtOpt) of those set-points has therefore been widely studied. However, due to the nonlinear dynamics of the HVAC system as well as the constraints associated with the system operation, real-time optimization always suffers from a heavy on-line computational load when those set-points are optimized simultaneously. To overcome this problem, multiplexed real-time optimization (MRtOpt) has been developed, which optimizes only one set-point at a time but with a faster optimization frequency. Because frequently resetting the set-points introduces artificial disturbances into the local control loops and may deteriorate the system stability, this paper presents a study to enhance the system stability of the multiplexed real-time optimization by integrating a degree of freedom (DOF) based set-point reset to renew the set-points instead of the conventional step-change set-point reset. The control performance of the integrated strategy was investigated using case studies. The results showed that around 10% of the energy saving was achieved by the proposed method compared with a method without real-time optimization. When compared with the conventional real-time optimization method, the proposed method resulted in around 70% computational load reduction, and over 26% reduction in the tracking errors of the local control loops.
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
Hussain Syed Asad, Richard Kwok Kit Yuen, Gongsheng Huang,