Abstract
Direct contact thermal energy storage (TES) for use in conventional air-conditioning systems is proposed to reduce the operational energy demand. Thermal performance of a novel kind of phase change material (PCM) prepared for use in conventional air-conditioning systems with the proposed direct contact TES tank, is evaluated. A 3-dimensional (3D) numerical model is built using ANSYS FLUENT to investigate dynamic characteristics of the discharging process of TES system. The model is validated by comparing the numerical with the experimental results. The effects of heat transfer fluid (HTF) flow rate, HTF inlet temperature, liquid PCM volume fraction, complete discharging time, discharging capacity of the tank, and temperature distribution in direct contact TES tank are investigated. The results indicate that increasing the HTF flow rate speeds up the discharging capacity and the discharging time of the direct contact TES system reduces. When the flow rate increases from 0.503Â m3/h to 0.936Â m3/h, the melting PCM increases from 63.33Â vol.% to 70.74Â vol.% within 600Â s. The discharging capacity increases with HTF inlet temperature; however, the whole discharging capacity does not change obviously by changing HTF inlet temperature.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
Xiao-Yan Li, Dong-Qi Qu, Liu Yang, Kai-Di Li,